| The following guide is for users who require guidance on their choice of isolator for a new installation. For a given application the choice is between DIN-rail mounting (MTL5000/MTL5500 range) and backplane mounting (MTL4000/MTL4500 range) devices.
If additional guidance is required, contact your local representative.
|
|
|
Analogue Input - 2-wire transmitters, 4-20mA conventional and ‘smart’
| | Device |
|
|
Important features |
| DIN-rail mounting devices |
| MTL5541 |
|
|
Compatible with most smart transmitters
|
| MTL5541A |
1 |
8.6V diode |
Separately powered smart transmitters
|
| MTL5541AS |
1 |
8.6V diode |
4 wire smart transmitters, current sink output | | MTL5541S |
1 |
16.5V min.
@20mA
|
Compatible with most smart transmitters, current sink output |
| MTL5544 |
2 |
|
Compatible with most smart transmitters
|
| MTL5544A |
2
|
8.6V diode |
Separately powered smart transmitters | | MTL5544AS |
2 |
8.6V diode |
4 wire smart transmitters, current sink output | | MTL5544D |
1 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters, repeat output
|
| MTL5544S |
2 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters, current sink output
|
| Backplane mounting devices |
| MTL4541 |
1 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters |
| MTL4541A |
1 |
8.6V diode |
Separately powered smart tranmitters
|
| MTL4541AS |
1 |
8.6V diode |
4 wire smart transmitter, current sink output
|
| MTL4541B |
1 |
16.5V min
@ 20mA
|
As MTL4541 but adapted for MTL4041B substitution on legacy backplanes
|
| MTL4541P |
1 |
17.6V min
@ 20mA
|
As MTL4541B but with a higher power output, MTL4041P substitution on legacy backplanes
|
| MTL4541S |
1 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters, current sink output
|
| MTL4544 |
2 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters |
| MTL4544A |
2
|
8.6V diode |
Separately powered smart transmitters
|
| MTL4544AS |
2 |
8.6V diode |
4 wire smart transmitters, current sink output
|
MTL4544B
|
1 |
16.5V min
@ 20mA
|
As MTL4544 but adapted for MTL4044B substitution on legacy backplanes |
| MTL4544D |
1 |
16.5V min
@ 20mA
|
Compatible with most smart transmitters, repeat output |
|
|
|
Analogue Input - vibration transducer
| | Device |
No. of
channels
|
Signal monitored |
Main features |
| DIN-rail mounting devices | |
| MTL5531 |
1 |
Vibration
transducer
|
Compatible with vibration and accelerometer transducers
| | |
|
|
|
| Backplane mounting devices |
| MTL4531 |
1 |
Vibration
transducer
|
Compatible with vibration and accelerometer transducers
|
|
|
|
Analogue Input - thermocouple and mV sources
| | Device |
No. of
channels
|
Output to
safe area
|
Main features |
| DIN-rail mounting devices | | MTL5573 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility |
| MTL5575 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility, alarm output
| | MTL5576-THC |
2 |
4/20mA |
Configurable, built-in CJC, also config as 1in 2 out
| | MTL5581 |
1 |
0 to ±50mV |
Selectable upscale or downscale
|
| Backplane mounting devices | | MTL4573 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility |
| MTL4575 |
1 |
4/20mA |
Configurable, built-in CJC, early burnout detection facility, alarm output
| | MTL4576-THC |
2 |
4/20mA |
Configurable, built-in CJC, also config as 1in 2 out | | MTL4581 |
1 |
0 to ±50mV |
Selectable upscale or downscale |
|
|
|
Analogue Input - 2, 3 and 4-wire RTDs
| | Device |
No. of
channels
|
Output to
safe area
|
Main features |
| DIN-rail mounting devices | | MTL5573 |
1 |
4/20mA |
Configurable, many sensor types and ranges |
| MTL5575 |
1 |
4/20mA |
Configurable, many sensor types and ranges, alarm output
|
| MTL5576-RTD |
2
|
4/20mA |
Configurable, also config as 1in 2 out
| | MTL5582B |
1 |
10 to 400 ohm |
Independent selection of 2, 3 or 4-wire RTDs on safe and hazardous area sides |
| Backplane mounting devices | | MTL4573 |
1 |
4/20mA |
Configurable, many sensor types and ranges |
| MTL4575 |
1 |
4/20mA |
Configurable, many sensor types and ranges, alarm output |
| MTL4576-RTD |
2 |
4/20mA |
Configurable, also config as 1in 2 out
|
|
|
|
|
Analogue Output - controller outputs, I/P converters
| | Device |
|
|
Important features |
| DIN-rail mounting devices |
| MTL5546 |
1 |
1mA Vmax = 16V <24ma
|
Suitable for HART valve positioners, SC & OC LFD |
| MTL5546Y |
1 | 1mA Vmax = 16V <24ma
|
Suitable for HART valve positioners, OC LFD |
| MTL5549 |
2 |
1mA Vmax = 16V <24ma
|
Suitable for HART valve positioners, SC & OC LFD |
| MTL5549Y |
2 |
1mA Vmax = 16V <24ma
|
Suitable for HART valve positioners, OC LFD |
| Backplane mounting devices |
| MTL4546 |
1 |
1mA Vmax = 16V <21.4ma
|
Suitable for HART valve positioners, SC & OC LFD |
| MTL4546Y |
1 |
1mA Vmax = 16V <26ma
|
Suitable for HART valve positioners, OC LFD |
| MTL4549 |
2 |
1mA Vmax = 16V <26ma
|
Suitable for HART valve positioners, SC & OC LFD |
| MTL4549Y |
2 |
1mA Vmax = 16V <24ma
|
Suitable for HART valve positioners, OC LFD |
|
|
|
Digital Input - switches / proximity detectors
| | Device |
|
|
Important features |
| DIN-rail mounting devices |
| MTL5510 |
4 |
4 x solid state |
Can switch +ve or –ve polarity signals |
| MTL5510B |
4 |
4 x solid state |
Mult-function selectable |
| MTL5511 |
1 |
1 x SPDT |
Switch/proximity detector repeater |
| MTL5513 |
2 |
2 x solid state |
dc to 500Hz frequency response |
| MTL5514 |
1 |
1 x SPDT
1 x SPDT
|
Switch/proximity detector repeater
Independent LFD output
| | MTL5514D |
1 |
2 x SPDT |
Dual output switch/proximity detector repeater |
| MTL5516C |
2 |
2 x SPDT |
Switch/proximity detector repeater | | MTL5517 |
2 |
2 x SPDT
1 x SPDT
|
Switch/proximity detector repeater
Independent LFD output
|
| Backplane mounting devices |
| MTL4504 |
1 |
1 x SPDT
1 x SPDT
|
Switch/proximity detector repeater
Independent LFD output, de-energise to alarm
| | MTL4510 |
4 |
4 x solid state |
Can switch +ve or –ve polarity signals |
| MTL4510B |
4 |
4 x solid state |
Mult-function selectable
switches +ve, -ve or ac signals
|
| MTL4511 |
1 |
1 x SPDT |
Switch/proximity detector repeater |
| MTL4513 |
2 |
2 x solid state |
dc to 500Hz frequency response
|
| MTL4514 |
1 |
1 x SPDT
1 x SPDT
|
Switch/proximity detector repeater
Independent LFD output, energise to alarm
| | MTL4514D |
1 |
2 x SPDT |
Dual output switch/proximity detector repeater |
| MTL4516 |
2 |
2 x SPST |
Switch/proximity detector repeater |
| MTL4516C |
2 |
2 x SPDT |
Switch/proximity detector repeater |
| MTL4517 |
2 |
2 x SPST
1 x SPDT
|
Switch/proximity detector repeater
Independent LFD output
|
|
|
|
Digital Input - switch/proximity detectors, SIL3
| | Device |
No. of
channels
|
Signals monitored |
Important features |
| DIN-rail mounting devices |
| MTL5501-SR |
1 |
24V logic |
Safety related, SIL3 certified
|
| Backplane mounting devices |
| MTL4501-SR |
1 |
24V logic |
Safety related, SIL3 certified
|
|
|
|
Digital Output - alarms, LEDs, solenoid valves, etc
| | Device |
|
|
Important features |
| DIN-rail mounting devices |
| MTL5521 |
1 |
12.8V Imax = 48mA <24v
|
IIC gas groups, loop powered |
| MTL5522 |
1 |
9.9V Imax = 70mA <21.4v
|
IIB gas groups, loop powered |
| MTL5523 |
1 |
12.8V Imax = 48mA <24v
|
Switch controlled input, Independent LFD output | | MTL5523V |
1 |
12.8V Imax = 48mA <24v
|
Voltage controlled input, Independent LFD output |
| MTL5524 |
1 |
12.8V Imax = 48mA <24v
|
Safety override feature, separately powered |
| MTL5525 |
1 |
7V Imax = 48mA <24v
|
Low power output, loop powered
|
| Backplane mounting devices |
| MTL4521 |
1 |
12.8V Imax = 48mA <24v
|
Loop powered | | MTL4521L |
1 |
10.3V Imax = 48mA <24v
|
Loop powered |
MTL4523
MTL4523R
|
1 |
12.8V Imax = 48mA <24v
|
Switch controlled input, Independent LFD output |
| MTL4523L |
1 |
12.8V Imax = 48mA <24v
|
Loop powered, independent LFD output | | MTL4523V |
1 |
12.8V Imax = 48mA <24v
|
Voltage controlled input, Independent LFD output |
MTL4524 &
MTL4524S
|
1 |
12.8V Imax = 48mA <24v
|
Safety override feature, separately powered |
| MTL4525 |
1 |
7V Imax = 48mA <24v
|
Safety override, low power output |
|
|
|
Digital Output - switch output to hazardous area
| | Device |
No. of
channels
|
Signals monitored |
Important features | | DIN rail mounting devices | | MTL5526 |
1 or 2 |
2 x DPDT |
Safe-area switch input or loop powered.
2ch or 1ch with 2 outputs
|
| Backplane mounting devices |
| MTL4526 |
1 or 2
|
2 x DPDT |
Safe-area switch input or loop powered.
2ch or 1ch with 2 outputs
|
|
|
|
Pulse Input - turbine / flowmeters
| | Device |
|
Input from
hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5532 |
1
|
Switch, proximity detector, current pulse, voltage pulse
|
Voltage and current inputs from 2 or 3-wire transmitters
configurable 4-20mA analogue output
|
| MTL5541 |
1 |
2-wire pulse |
e.g. 2-wire turbine and vortex flowmeters |
| Backplane mounting devices |
| MTL4532 |
1 |
1mA Vmax = 16V <21.4ma
|
Voltage and current inputs from 2 or 3-wire transmitters
configurable 4-20mA analogue output
|
| MTL4541 |
1 |
2-wire pulse |
e.g. 2-wire turbine and vortex flowmeters |
|
|
|
Fire / Smoke detectors
| | Device |
No. of
channels
|
Output to
hazardous area
|
Important features |
| DIN-rail mounting devices |
| MTL5561 |
2 |
Loop powered |
0–40mA, fire and smoke detectors |
| Backplane mounting devices |
| MTL4561 |
2 |
Loop powered |
0–40mA, fire and smoke detector |
|
|
|
Signal transfer - safe area to safe area - via hazardous area
| Device
pair
|
No. of
channels
|
Signal transferred |
Important features |
| DIN-rail mounting devices |
MTL5546Y &
MTL5541A
|
1 |
4/20mA smart
|
Driver
Receiver
| MTL5526 &
MTL5516C
|
2 |
Status signals |
Driver, relay output
Receiver, digital output
|
| MTL5051 |
1 |
RS232 or RS422 |
Either can be used as receiver or driver |
| Backplane mounting devices |
MTL4546Y &
MTL4541A
|
1 |
4/20mA smart
|
Driver
Receiver
| MTL4526 &
MTL4516
|
2 |
Status signals |
Driver, relay output
Receiver, digital output
|
|
|
|
Trip amplifiers
| | Device |
No. of
channels
|
Signals monitored |
Important features |
| DIN-rail mounting devices |
| MTL5314 |
1 |
4/20mA |
Configurable, one or two alarms |
|
|
|
|