| Choosing
a Barrier - by application |
| The MTL7700 Series, with
their advanced features, should be regarded as your first
choice for all new designs or installations. The recommendations
below are based therefore on the MTL7700 Series.
Users of MTL700, 4700 or 7000 Series products
can also use the guide because of MTL's consistent numbering
policy. Products, in any barrier series, that have the same
two last digits (ignoring letters and '+' symbols) will have
very similar characteristics, e.g. MTL7787 and MTL787 or MTL7087.
A table of alternatives to earlier
barrier models is also available, click for details
> 
|
| Analogue
Input - 2-wire transmitters, 4-20mA conventional and 'smart' |
| Power Supply |
Barrier |
Loops
|
Voltage
for Tx
and lines |
Main features |
| Regulated |
MTL7787+ |
|
12.4V
|
Compatible with most smart Tx's |
| MTL7787P+ |
1 |
13.1V |
Higher power, IIC gases |
| MTL7788R+ |
1 |
13.7V |
1-5V safe area ouput |
Unregulated
20 to 35V |
MTL7706+ |
1 |
15.5V
(250ohm load) |
High accuracy; compatible with most smart transmitters;
full output voltage
available independently of supply voltage |
| MTL7707P+ |
1 |
13.0V |
Higher power, IIB gases |
|
| Analogue
Input - vibration probes |
| Power Supply |
Barrier |
Loops
|
Main features |
| Regulated |
MTL7796– |
1 |
For –24V systems |
|
| Analogue
Input - gas detectors |
| Power Supply |
Barrier |
Loops
|
Main features |
| Nominal 6V supplies |
MTL7758+ |
1 |
For high current/low voltage
MTL7758+ Vwkg = 6.0V |
|
| Analogue
Input - thermocouple & mV sources |
| Power Supply |
Barrier |
Loops
|
Max end to enc
resistance
per loop |
Main features |
Earth-free signal, receiver
input floating |
MTL7760ac |
1 |
150 ohm |
– |
| Moving coil or low resistance receivers |
MTL7755ac |
1 |
38 ohm |
– |
|
| Analogue
Input - ac sensors, photocells, microphones & flowmeters |
| Power Supply |
Barrier |
Loops
|
Max end to enc
resistance
per loop |
Main features |
Earth-free signals up to
a few kHz |
MTL7760ac |
1 |
150 ohm |
– |
|
| Analogue
Input - slidewire displacement transducers |
| Power Supply |
Barrier |
Loops
|
Vwkg |
Main features |
For nominal
6V supplies |
MTL7760ac |
1 |
6.0V |
– |
|
| Analogue
Input - 2, 3 and 4-wire RTDs |
| Power Supply |
Barrier |
Loops
|
Main features |
| 2-wire |
MTL7755ac |
|
2 channels track to 0.15 ohm |
| 3-wire |
MTL7755ac |
2/3 |
End-to-end resistance 19 ohm/channel |
| MTL7756ac |
1 |
End-to-end resistance 19 ohm/channel |
| 4-wire |
MTL7755ac |
1/2 |
Needs 2 barriers |
| MTL7760ac |
1/2 |
Vwkg = 6V; needs 2 barriers |
| MTL7761ac |
1/2 |
Vwkg = 6V; needs 2 barriers |
|
| Analogue
Input - strain-gauge bridges (single) |
| Power Supply |
Barrier |
Loops
|
Volts for 350 ohm bridge |
| IIC gases |
MTL7761ac (2) +
MTL7764ac (1) |
1 |
9.75V from MTL7766Pac with 20V supply |
|
| Analogue
Input - strain-gauge bridges (multiple) |
| Power Supply |
Barrier |
Loops
|
Volts for
350 ohm bridge (20V in)
Number of bridges
1.............2..........3............4 |
| IIC gases |
MTL7761ac (2) +
MTL7766ac (1) |
1 |
13.0........9.2.......7.7.........6,2 |
|
| Analogue
Output - controller outputs (I/P converters) |
| Power Supply |
Barrier |
Loops
|
Volt drop
at 20mA |
Main features |
| Output goes to 0V (earth return);
regulated supplies |
MTL7728+ |
|
6.8V |
– |
| MTL7728P+ |
1 |
5.1V |
Higher power, IIC gases |
| MTL7729P+ |
1 |
3.7V |
Higher power, IIB gases |
| Transistor between controller
output and 0V; (diode return); regulated supplies |
MTL7787+ |
1 |
8.1V |
– |
| MTL7787P+ |
1 |
6.4V |
Higher power, IIC gases |
| Transistor between controller
output and 0V; (diode return); unregulated supplies (20
to 35V) |
MTL7707+ |
1 |
8.6V |
– |
| MTL7707P |
1 |
6.0V |
Higher power, IIC gases |
|
| Digital
Input - switches |
| Power Supply |
Barrier |
Loops
|
Main features |
| Regulated |
MTL7787+ |
1 |
Diode return |
| MTL7787P+ |
1 |
|
| MTL7789+ |
2 |
|
|
| Digital
Input - switches / proximity detectors |
| Power Supply |
Barrier |
Loops
|
Main features |
| Unregulated 22-35V |
MTL7741 |
1 |
Changeover relay output |
| MTL7742 |
1 |
Transistor output, fast switching |
| MTL7743 |
2 |
2 x relay contacts |
| MTL7744 |
2 |
2 x transistor output |
| MTL7745 |
1 |
Single channel relay + LFD |
|
| Digital
Output - alarms, LEDs, solenoid valves, etc |
| Power Supply |
Barrier |
Loops
|
Usable power per
loop |
Main features |
| Switch in power leg, (earth
return); regulated supplies |
MTL7728+ |
|
0.48W |
– |
| MTL7728P+ |
1 |
0.59W |
Higher power, IIC gases
Voltage drop = 5.1V at 20mA |
| MTL7729P+ |
1 |
0.82W |
Higher power, IIB gases |
| Control switch on earth (diode
return); regulated supplies |
MTL7787+ |
1 |
0.42W |
– |
| MTL7787P+ |
1 |
0.51W |
Higher power, IIC gases |
| Transistor between controller
output and 0V; (diode return); unregulated supplies (20
to 35V) |
MTL7707+ |
1 |
0.29W |
Up to 35mA available |
| MTL7707P+ |
1 |
0.68W |
Optimised for IIB gases |
|
| Digital
Input/Output - –ve and floating supplies |
| Power Supply |
Barrier |
Loops
|
Volts for 350
ohm bridge |
Regulated negative/floating
power supply |
MTL7728– |
1 |
– |
|
| 2-wire
DC/AC systems - signal returns |
| System or Function |
Barrier |
Loops
|
Vwkg |
Main features |
| 6V dc systems |
MTL7710+ |
|
6.0V |
– |
| 8V dc system |
MTL7710P+ |
1 |
8.0V |
End ot end resistance 42 ohm.
5V at 65mA from 8V supply. IIC gases |
| Low-level logic returns |
MTL7764+ |
2 |
10.0V |
End-to-end resistance 1050 ohms |
| 12V dc systems |
MTL7715+ |
1 |
12.0V |
– |
| MTL7715P+ |
1 |
12.6V |
– |
| 18V dc systems |
MTL7722+ |
1 |
19.6V |
– |
| 2-wire dc/ac systems |
MTL7778ac |
1 |
24.0V |
– |
| Signal returns |
MTL7789+ |
2 |
26.6V |
2 diode return channels + power |
| Securing cables to earth for future use;
terminating cable screens |
MTL7799 |
– |
– |
Bussed power feed - not certified |
|
|
|
| |
 |
|
|
|