Notes on Circuit A
- Classification: ia IIC
- Cable parameters: 1000µF, 350 mH
- Earthed at RTD
Note: T class determined by maximum measured temperature
--------------------------------------------------------------------------------------------------
RTD Type: 350L (example)
Peter Pty, Sydney, Australia
Simple Apparatus to IEC 60079-11
Passive component to subclause 5.4a)
Type: PS061
Maximum operating temperature 450°C
Temperature classification determined by maximum measured
temperature.
Note: If cable 'x' becomes part of a multicore, then this
multicore
cable must be a Type 'A' or 'B', as specified in IEC 60079-14.
RTD suitable for Zone 0 / Zone 1 interface